Measuring range
|
0-60MPa, More than 60Mpa needs to be customized.
|
Pressure type
|
Positive pressure(Include gauge pressure and sealing gauge pressure)
|
Accuracy level
|
±0.5%FS±025%FS(Test conditions: temperature 20±2℃; Air pressure:86-106kPa; Humidity:45%RH-75%RH)
|
Operating temperature
|
-40-80℃
|
Temperature drift
|
≤0.03%FS/℃
|
Annual stability
|
≤0.2%FS/ year typical; ≤0.5%FS/ year maximum
|
Supply voltage
|
12-30VDC
|
Current load
|
< (U-10)/0.02Ω[U: power supply voltage]
|
Output signal
|
Two-wire 4-20mA; Three-wire 0.5-4.5VDC ,1-5VDC 0-5VDC ;Four-wire Rs485 digital output, etc.
|
Insulation strength
|
Withstand voltage of 500V without breakdown
|
Insulation resistance
|
>500MΩ
|
Frequency response
|
Sensor < 10ms;; Transmitter ≤15ms
|
Life
|
> 1 million pressure cycles
|
Explosion-proof mark
|
ExiaIICT6 Intrinsically Safe and Explosion-proof (only valid for explosion-proof type)
|
Electrical parameter
|
HSM connector (wire diameter φ4.5-φ7mm) or cable lm
|
Applicable medium
|
solid that do not react chemically with structural materials (probe materials, sealing materials)
|
Probe base material
|
Stainless steel etc
|
Probe seal material
|
All-welded structure without sealing material
|
Protection level
|
IP65 IP67 IP68
|
Weight
|
About 150g-10kg[ different due to different subtypes of application]
|
Atmospheric pressure
|
60-110KPa;ambient humidity: ≤95%RH;Storage temperature: -40-120℃
|
Vibration
|
Under the condition of 10gRMS and 20-2000 Hz, the change is less than 0.5%FS
|
Shock
|
100g, and the change after 10ms impact is less than 0.5%FS (only for general-purpose effective general-purpose models, the maximum
allowable impact is 120g) |
Interfererce
|
Under the interference of 10-300MHZ and field strength of 10V/m, the error is less than 0.5%FS
|